Hello!Welcome to Madshen.
hotsearch
MDSB308E series end detection switch safety barrier

 

undefined


function

MDSB308E series end detection Isolation type switch Safety gate Receive from the dangerous places such as signal switches, proximity switch, isolation and output. Optional One enter One A, One enter Two A, Two enter Two A. Isolated gate From the terminal energy into the limit of intrinsically safe dangerous places, so as to ensure the safety and explosion-proof system.

 

Type specification

Product model

1 input code

2 input code

The output of the 1 code

The output of the 2 code

MDSB308E-

1: passive switch

1: passive switch

1: passive relay

1: passive relay

2: active switch

2: active switch

2: passive collector

2: passive collector

G: other signals

G: other signals

4: active output

4: active output


0: input 2

G: other signals

G: other signals




0: output 2

 

 Undefined

 

Explosion-proof technology index

Explosion proof mark: [Exia Ga] II C

Authentication parameters: (terminal 4/6 , 1/3 Between)

Um=250V Uo=11V Io=14mA

Po=39mW Co=1.4 Mu F Lo=60mH


 

Product features:

The input and output power, the three party is completely isolated, strong anti-interference ability

High precision, high linearity, high stability

Modular design, small volume, low power consumption, suitable for intensive installation

Reasonable structure, easy plugging, installation, disassembly and maintenance is more convenient and simple 

Technical indicators

The working power supply: 24VDC . 10%

Work    Consumption: less than or equal to 2W ( Two enter Two (a) passive output)

Less than or equal to 3W ( Two enter Two (a) active output)

The input signal (danger zone):

Passive switch input (contact):

Short circuit current: 8mA

The open circuit voltage: 8V

The loop current is less than or equal to 1.2mA "Guan said"

The loop current is greater than or equal to 2.1mA Said ""

Active switch input:

Order negotiation technology index

The output signal (safety):

    Passive relay output:

        Contact type: normally open

Contact capacity: 0.2A /30VDC

    Passive collector output:

        External power supply: less than or equal to 30VDC

The load current is less than or equal to: 60mA

Active output: high level over 20V The low level is less than or equal; 3V

The maximum output power 24VDC/30mA

The switching frequency is less than or equal to: 5kHz (collector output)

Less than or equal to 20Hz (relay output)

Dielectric strength: input / The output is more than 2000VAC ( 1min )

input / The power is greater than or equal to 2000VAC ( 1min )

output / The power is greater than or equal to 1000VAC ( 1min )

Intrinsically safe / Non intrinsically safe, more than 2000VAC ( 1min )

Insulation resistance: input / output / The power is greater than or equal to 100M (omega 500VDC )


Common specifications selection examples:

 

Model:MDSB308E-1010

Passive Input: switch signal

Output1:Passive relay signal

Aux.power:24VDC

Description: This product is a DC power supply type detection terminalIsolation switchSafety gate,      Passive switch signalInput,  After isolating the output  Passive relay signalThe auxiliary power supply for 24VDC.;

For details please download: MDSB308E detection end switch Isolated gate   


Tags: MDSB308E   detection end switch   isolation type safety grid  