Author:
madshen Add Time:2014-04-02 19:05:02
Function overview
MDSE102 series Three combination of alternating current Transmitter The alternating current is detected in proportion to convert the DC voltage or current signal. Transmitter Is a measure of average value according to the effective value, not the true effective value measurement, if the input waveform distortion, the output will generate additional error.
Specifications
Three combination of alternating currentTransmitter | Input current code | Output signal code | The auxiliary power supply + function code |
MDSE102- | 1:0~1A | 1:0~5V | 12:DC24V |
2:0~2A | 2:1~5V | 32:AC220V |
3:0~5A | 3:0~20mA |
|
4:0~10A | 4:4~20mA |
|
0 other ranges: | 0 other ranges: |
|

Technical indicators
Input signal: alternating current, see table
Input power absorption: Less than or equal to 0.1VA Each input ( 5A )
Input overload capacity: Two Times of continuous input current
Thirty Times, One Second current input
Input frequency range: 45Hz~55Hz
Output signal: DC voltage or current, see table
Multi output is the reference terminal
Output: output voltage, load or load 5K Omega
The current output load is less than or equal to Five hundred and fifty Omega
Conversion accuracy: + 0.5%F.S (typ. 0.2%F.S )
Response time: 300ms
Isolation mode: input, output, power supply isolated
Not isolated output
Insulation resistance: 200M Omega /DC500V
Dielectric strength: input / output / Power Supply 2000VAC/1min
The auxiliary power supply: DC24V . 10% Less than or equal. 3W
AC86~265V Less than or equal. 5VA