MDSB321E series detection terminal current isolation type sa

 

undefined


function

MDSB321E series of isolated terminal current detection Safety gate (HART) Sampling risk areas Four Intelligent wireTransmitter Output 4~20mA+HART After processing the output signal isolation. This product is compatible with HART communicationCan be used for intelligent. Transmitter . Optional One enter One A, One enter Two A, Two enter Two A. Isolated gate From the terminal energy into the limit of intrinsically safe dangerous places, so as to ensure the safety and explosion-proof system.

 

Type specification

Product model

1 input signal

2 input signal

The 1 output signal

The 2 output signal

MDSB321E-C0C0

4~20mADC+HART

No input 2

4~20mADC+HART

Output 2

MDSB321E-C0CC

4~20mADC+HART

No input 2

4~20mADC+HART

4~20mADC

MDSB321E-CCCC

4~20mADC+HART

4~20mADC+HART

4~20mADC+HART

4~20mADC+HART

 

 Undefined

 

Explosion-proof technology index

Explosion proof mark: [Exia Ga] II C

Authentication parameters: (terminal 4/6 Between, 1/3 Between)

Um=250V Uo=28V Io=93mA

Po =655mW Co=50nF Lo=2.4mH

 

 

Product features:

The input and output power, the three party is completely isolated, strong anti-interference ability

High precision, high linearity, high stability

Modular design, small volume, low power consumption, suitable for intensive installation

Reasonable structure, easy plugging, installation, disassembly and maintenance is more convenient and simple

 

 

Technical indicators

The working power supply: 24VDC . 10%

Work    Consumption: less than or equal to 1.0W ( One enter One A)

Less than or equal to 1.8W ( One enter Two A)

Less than or equal to 2.0W ( Two enter Two A)

Input signal: danger zone, 4~20mA+HART

Input impedance: less than or equal to Two hundred Omega

Output signal: 4~20mA+HART The safety zone,

Output load: 0~350 Omega, use HART Must be greater than Two hundred and thirty Omega

One enter Two A model of output Two nothing HART function

Conversion accuracy: + 0.1%F.S

Temperature drift:. 0.01% F.S/ C

Dielectric strength: input / The output is more than 2000VAC ( 1min )

input / The power is greater than or equal to 2000VAC ( 1min )

          output / The power is greater than or equal to 1000VAC ( 1min )

          Intrinsically safe / Non intrinsically safe, more than 2000VAC ( 1min )

Insulation resistance: input / output / The power is greater than or equal to 100M (omega 500VDC )

 

Remarks: One enter One A model, One , Three , Eleven , Twelve Don't pick feet up; One enter Two A model, One , Three Don't pick feet up. -US>/ is a non intrinsically safe. 2000VAC ( 1min )

 

Insulation resistance: input / output / The power is greater than or equal to 100M (omega 500VDC )

 

Common specifications selection examples:

 

Model:MDSB321E-C0C0-1212

Input: 4-20mADC+HART signal

Output1:4-20mADC+HART signal

Aux.power:24VDC

Description: This product is a DC power supply typeThe detection terminal current isolationSafety gate,  4-20mADC+HART signalInput, After isolating the output after treatment4-20mADC+HARTThe auxiliary power supply for 24VDC. signal;