Hello!Welcome to Madshen.
hotsearch
MDSB303E series thermocouple thermal isolation type safety g

 

undefined


function

MDSB303E series Thermocouple temperature isolation type Safety gate yes The scene K , S , E , B , R , T , J , N Thermocouple etc. sensor The output signal, After isolating the linear processing, and converted into a linear relationship between the voltage or current signal output and temperature. Optional One enter One A, One enter Two A. Online index number and temperature range. Isolated gate From the terminal energy into the limit of intrinsically safe dangerous places, so as to ensure the safety and explosion-proof system.

 

Type specification

Product model

1 input code

2 input code

The output of the 1 code

The output of the 2 code

MDSB303E-

1:K type thermocouple

0: input 2

2:0~5VDC

2:0~5VDC

2:S type thermocouple


3:1~5VDC

3:1~5VDC

3:E type thermocouple


B:0~20mADC

B:0~20mADC

4:B type thermocouple


C:4~20mADC

C:4~20mADC

5:R type thermocouple


G: other signals

G: other signals

6:T type thermocouple



0: output 2

7:J type thermocouple




8:N type thermocouple




G: other thermocouple




 

 Undefined

 

Explosion-proof technology index

Explosion proof mark: [Exia Ga] II C

Authentication parameters: (terminal 4/6 Between)

Um=250V Uo=6.6V Io=68mA

Po=113mW Co=5 Mu F Lo=5mH

 

Technical indicators

The working power supply: 24VDC . 10%

Work    Consumption: less than or equal to 1.0W ( One enter One A)

Less than or equal to 1.5W ( One enter Two A)

Input signal: K , S , E , B , R , T , J And the danger zone

Cold end compensation: 0~50 Degree of error One C

Output signal: DC voltage or current signal safety zone

Output: output current, 0~350 Omega

The output voltage is greater than or equal. 10K Omega

Conversion accuracy: + (0.2%F.S Delta V>10mV)

          . 0.4%F.S (10mV More than Delta V More than 5mV)

Temperature drift:. 100ppm/ C

Dielectric strength: input / The output is more than 2000VAC ( 1min )

input / The power is greater than or equal to 2000VAC ( 1min )

          output / The power is greater than or equal to 1000VAC ( 1min )

          Intrinsically safe / Non intrinsically safe, more than 2000VAC ( 1min )

Insulation resistance: input / output / The power is greater than or equal to 100M (omega 500VDC )



Remarks: Safety gate The connection between the thermocouple compensation wire to must use the same type, otherwise it will increase the measurement error.


CJC is used for thermocouple cold junction compensation, has been fixed on the special terminal.

1 into 1 types, 11, 12 feet up with.

Product features:

The input and output power, the three party is completely isolated, strong anti-interference ability

High precision, high linearity, high stability

Modular design, small volume, low power consumption, suitable for intensive installation

Reasonable structure, easy plugging, installation, disassembly and maintenance is more convenient and simple

 

Common specifications selection examples:

 

Model:MDSB303E-10C0

Input: type K thermocouple indexing

Output1:4-20mADC signal

Aux.power:24VDC

Description: This product is a DC power supply typeThermocouple temperature changeIsolated gate,   K type thermocouple indexing  Input, After isolation after transmission output4-20mADCThe auxiliary power supply for 24VDC. signal;

For details please download: MDSB303E series of thermocouple temperature change Isolated gate 


 

 

 

Tags: MDSB303E   thermocouple temperature change   isolation type safety grid  
Browse:
Return To The Top

分享到: