Hello!Welcome to Madshen.
hotsearch
MDSB306E series detection converter safety barrier

 

undefined


function
MDSB306E series Detection of isolated converter Safety gate yes Linear voltage or current signal, receiving a dangerous place after isolation, transformed into linear signal output to the user specified, safe area. Optional One enter One A, One enter TwoA, Two enter Two A. Isolated gate From the terminal energy into the limit of intrinsically safe dangerous places, so as to ensure the safety and explosion-proof system.

 

Type specification

Product model

1 input code

2 input code

The output of the 1 code

The output of the 2 code

MDSB306E-

1:0~1VDC

1:0~1VDC

1:0~1VDC

1:0~1VDC

2:0~5VDC

2:0~5VDC

2:0~5VDC

2:0~5VDC

3:1~5VDC

3:1~5VDC

3:1~5VDC

3:1~5VDC

4:0~10VDC

4:0~10VDC

4:0~10VDC

4:0~10VDC

A:0~10mADC

A:0~10mADC

A:0~10mADC

A:0~10mADC

B:0~20mADC

B:0~20mADC

B:0~20mADC

B:0~20mADC

C:4~20mADC

C:4~20mADC

C:4~20mADC

C:4~20mADC

G: other signals

G: other signals

G: other signals

G: other signals


0: input 2


0: output 2

 

 Undefined

 

Explosion-proof technology index

Explosion proof mark: [Exia Ga] II C

Authentication parameters: (terminal 4/6 Between, 1/3 Between)

Um=250V Uo=28V Io=93mA

Po =655mW Co=50nF Lo=2.4mH

 

Technical indicators

The working power supply: 24VDC . 10%

Work    Consumption: less than or equal to 1.2W ( One enter One A)

Less than or equal to 1.8W ( One enter Two A)

Less than or equal to 2.4W ( Two enter Two A)

Input signal: DC current or voltage signal, the danger zone

Input impedance: current input is less than or equal to Two hundred Omega;

The input voltage is greater than or equal. 500K Omega

Output signal: DC current or voltage signal, the safety zone

Output: output current, 0~350 Omega;

The output voltage is greater than or equal. 10K Omega

Conversion accuracy: + 0.2%F.S

Temperature drift:. 0.01% F.S/ C

Dielectric strength: input / The output is more than 2000VAC ( 1min )

input / The power is greater than or equal to 2000VAC ( 1min )

          output / The power is greater than or equal to 1000VAC ( 1min )

          Intrinsically safe / Non intrinsically safe, more than 2000VAC ( 1min )

Insulation resistance: input / output / The power is greater than or equal to 100M (omega 500VDC )


Product features:

The input and output power, the three party is completely isolated, strong anti-interference ability

High precision, high linearity, high stability

Modular design, small volume, low power consumption, suitable for intensive installation

Reasonable structure, easy plugging, installation, disassembly and maintenance is more convenient and simple

 

Remarks: One enter One A model, One , Three , Eleven , Twelve Don't pick feet up; One enter Two A model, One , Three Don't pick feet up.

 

 

Common specifications selection examples:

 

Model:MDSB306E-20C0

Input: 0-5VDC signal

Output1:4-20mADC signal

Aux.power:24VDC

Description: This product is a DC power supply type detection terminalThe conversion and isolationSafety gate,   0-5VDC signal Input, After isolating the output after treatment4-20mADCThe auxiliary power supply for 24VDC. signal;

For details please download: The conversion of MDSB306E detection terminal Isolated gate 


Tags: MDSB306E,检测端转换,隔离式安全栅  
Browse:
Return To The Top

分享到: