MDSB301E detection terminal current safety barrier


Summary

MDSB302E series Isolated Safety gate Mounted as a guide rail, the base and the host can be separated from the plug, easy installation and maintenance. This series Safety gate A variety of products, can handle the current, voltage, thermal resistance, thermocouple, switch and other industrial products are widely signal. Used in chemical, petroleum, metallurgy, electric power, natural gas and other industries, connect with all kinds of this instrument, as the use of explosion-proof system and related equipment.

Products comply with " GB3836.1-2010 Explosive environment No. One Part: General requirements for equipment "and" GB3836.4-2010 Explosive environment No. Four Part: the intrinsic safety type" I "Protection equipment", through the China explosion-proof inspection agencies strict test qualified, And made explosion-proof certification.

 Undefined

 

function

Sampling risk area Four Wire Transmitter The output current signal, after isolating output after treatment. Optional One enterOne A, One enter Two A, Two enter Two A. Isolated gate From the terminal energy into the limit of intrinsically safe dangerous places, so as to ensure the safety and explosion-proof system.

 

Type specification

Product model

1 input signal

2 input signal

The 1 output signal

The 2 output signal

MDSB301E-C0C0

4~20mADC

No input 2

4~20mADC

Output 2

MDSB301E-C0CC

4~20mADC

No input 2

4~20mADC

4~20mADC

MDSB301E-CCCC

4~20mADC

4~20mADC

4~20mADC

4~20mADC

 

 Undefined

 

Explosion-proof technology index

Explosion proof mark: [Exia Ga] II C

Authentication parameters: (terminal 4/6 Between, 1/3 Between)

Um=250V Uo=28V Io=93mA

Po =655mW Co=50nF Lo=2.4mH

 

 

Product features:

The input and output power, the three party is completely isolated, strong anti-interference ability

High precision, high linearity, high stability

Modular design, small volume, low power consumption, suitable for intensive installation

Reasonable structure, easy plugging, installation, disassembly and maintenance is more convenient and simple

 

 

Technical indicators

The working power supply: 24VDC . 10%

Work    Consumption: less than or equal to 1.8W ( One enter One A)

Less than or equal to 1.2W ( One enter Two A)

Less than or equal to 1.6W ( Two enter Two A)

Input signal: Four Wire 4~20mA And the danger zone

Maximum input: 30mA

Input impedance: less than or equal to Two hundred Omega

Output signal: Four Wire 4~20mA The safety zone,

Output load: 0~350 Omega

Conversion accuracy: + 0.1%F.S

Temperature drift:. 0.01% F.S/ C

Dielectric strength: input / The output is more than 2000VAC ( 1min )

input / The power is greater than or equal to 2000VAC ( 1min )

          output / The power is greater than or equal to 1000VAC ( 1min )

          Intrinsically safe / Non intrinsically safe, more than 2000VAC ( 1min )

Insulation resistance: input / output / The power is greater than or equal to 100M (omega 500VDC )

Note: 1 in 1 out of 1, 3, 11, and 12 feet up with 1; in 2 out of 1 models, 3 feet up, don't answer.

 

Common specifications selection examples:

 

Model:MDSB301E-C0C0-1212

Input: 4-20mADC signal

Output1:4-20mADC signal

Aux.power:24VDC

Description: This product is a type of detection of DC power supply terminal current isolationSafety gate,  4-20mADC signal Input, After isolating the output after treatment4-20mADCThe auxiliary power supply for 24VDC. signal;