Technical characteristics of mdsf1-ai4 detection end distrib

Functional specifications

MDSF1 - AI4 detection terminal distribution type safety barrier for the dangerous sites (HART) to work power source to provide 2 wire system of transmitter, and sampling of the transmitter output current signal (compatible with HART), after separation output to the DCS/PLC. The working power is taken from the output loop and does not require an independent power supply. Explosion-proof grade Exib Gb Ⅱ C. You can choose 1 out of 1 and 2 out of 2.

Industry application

2 wire intelligent transmitter, non-intelligent transmitter, 4~20mA + HART signal.

Explosion-proof indicators

Explosion-proof marks: [Exib Gb] Ⅱ C

Authentication parameters: (terminal 7-8, terminal 9-10)

Io Um = 250 v Uo = 28 v = 30 ma

Co = 50 nf Lo Po = 840 mw = 0.5 mH

Technical indicators

Working power: 21 ~ 30VDC, output signal power supply

Input signal: danger side, 2 wire system, 4 ~ 20mA + HART

Distribution voltage: 16-28v

Distribution protection: maximum short circuit current, 30mA

Maximum open circuit voltage, 28V

Output signal: security side, 4 ~ 20mA + HART, sink mode

Error @ 25 ℃, 0.3% or less F.S (typically 0.2% F.S.)

Temperature drift: 0.005% or less F.S / ℃

Response time: 50ms

Insulation strength: input - output, greater than 2500VAC (1min)

Insulation resistance: the input - output, 200 m or more Ω (500 VDC)


 