MDSE106 series of six alternating current collector

  Function overview
MDSE106 series Six AC current collector Testing Six AC current signal, through the RS485 The bus transfer to DCS System.

 

Specifications

Six AC current collector

Input current code

measuring method

The auxiliary power supply

communication Agreement

MDSE106-

1:0~1A

0: (note)

1:DC24V

1:MODBUS-RTU

2:0~2A

1: the true effective value

3:AC220V

2:PROFIBUS-DP

3:0~5A




4:0~10A




0 other ranges:




 

 

Remarks: The average measured according to the effective value, not the true effective value measurement, if the input waveform distortion will generate additional error.

 

 Undefined

 

Technical indicators


Input signal: alternating current, see table

Input power absorption: Less than or equal to 0.1VA Each input ( 5A )

Input overload capacity: Two Times of continuous input current

Thirty Times, One Second current input

Input frequency range: 45Hz~55Hz

Refresh data: One second

Measurement error: + 0.5%F.S (typ. 0.2%F.S )

communication Address: 1~247

Baud rate: One thousand and two hundred , Two thousand and four hundred , Four thousand and eight hundred , Nine thousand and six hundred , Nineteen thousand and two hundred

Isolation mode: input, output, power supply isolated

Insulation resistance: 200M Omega /DC500V

Dielectric strength: input / output / Power Supply 2000VAC/1min

The auxiliary power supply: DC24V . 10% Less than or equal. 1W

AC86~265V Less than or equal. 2VA