Hello!Welcome to Madshen.
hotsearch
MDSE104 series three-phase power factor transmitter

Function overview

MDSE104 series Three-phase power factor Transmitter That single chip as the core, using the new algorithm, the accurate measurement of AC circuit power factor, in proportion to convert the DC voltage or current signal.

 

Specifications

Three phase power

factorTransmitter

Transmission function

Code

input voltage

Code

Input current

Code

output signal

Code

The auxiliary power supply

Code

power factor

MDSE104-

3-: three-phase three wire power factor

1:0~100V

1:0~1A

1:4~20mA

1:DC24V

-C1:0 (C) ~1~0 (L)

4-: three-phase four wire power factor

2:0~200V

2:0~5A

2:4~12~20mA

3:AC220V

-C2:0.5 (C) ~1~0.5 (L)


3:0~270V

3:0~10A

3:0~5V


-C3:0~1


4:0~400V

0 other ranges:

4:0~ + 5V




0 other ranges:


0 other ranges:



 

 

 Undefined

 

Technical indicators


Input power: less than or equal to absorption 0.2VA Each input ( 100V )

Less than or equal to 0.1VA Each input ( 5A )

Input overload capacity: Two Times of continuous input current

Thirty Times, One Second current input

Two Times, continuous input voltage

Input frequency range: 45Hz~55Hz

Output signal: DC voltage or current, see table

Output: output voltage, load or load 5K Omega

          The current output load is less than or equal to Five hundred and fifty Omega

Conversion accuracy: + 0.2%F.S

Response time: 400ms

Isolation mode: input, output, power supply isolated

Insulation resistance: 200M Omega /DC500V

Dielectric strength: input / output / Power Supply 2000VAC/1min

The auxiliary power supply: DC24V . 10% Less than or equal. 3W

AC86~265V Less than or equal. 5VA

 

 

For details please download:MDSE104 series three-phase power factorTransmitter


Browse:
Return To The Top

分享到: