MDSC322E series distribution isolator (HART)

Product introduction

 

MDSC322E series distribution isolator (HART) Mounted as a guide rail, the base and the host can be separated from the plug, easy installation and maintenance. Series of products rich, can handle the current, voltage, thermal resistance, thermocouple, switch and other industrial products are widely signal. The application in building material, metallurgy, electric power and other industries, effectively restrain all kinds of interference signal.

 

 Undefined

function

This product is compatible with the distribution and isolation Two Modes: distribution mode, to the scene Two Wire TransmitterSupply, sampling Transmitter Output Two Wire current signal through the isolation after processing into Four Wire current isolation mode, sampling signal output; Four Wire current signal through the isolation output Four Wire current signal. The toggle switch product side built-in can set the input mode. This product is compatible with HART communication Can be used for intelligent. Transmitter . Optional One enter One A, One enter Two A, Two enter Two A.

Type specification

Product model

1 input signal

2 input signal

The 1 output signal

The 2 output signal

MDSC322E-C0C0

4~20mADC+HART

No input 2

4~20mADC+HART

Output 2

MDSC322E-C0CC

4~20mADC+HART

No input 2

4~20mADC+HART

4~20mADC

MDSC322E-CCCC

4~20mADC+HART

4~20mADC+HART

4~20mADC+HART

4~20mADC+HART

 

 Undefined

 

Product features:

The input and output power, the three party is completely isolated, strong anti-interference ability

High precision, high linearity, high stability

Modular design, small volume, low power consumption, suitable for intensive installation

Reasonable structure, easy plugging, installation, disassembly and maintenance is more convenient and simple

Technical indicators

The working power supply: 24VDC . 10%

Work    Consumption: less than or equal to 1.2W ( One enter One A)

Less than or equal to 1.8W ( One enter Two A)

Less than or equal to 2.4W ( Two enter Two A)

Input signal

Distribution mode, Two Wire 4~20mA+HART

Isolation mode, Four Wire 4~20mA+HART

Voltage distribution: distribution mode, 19~26V

Distribution: the maximum short-circuit current protection, 40mA

          The maximum open circuit voltage, 26V

Input impedance: isolation mode, less than or equal to Two hundred Omega

Output signal: Four Wire 4~20mA+HART

Output load: 0~350 Omega, use HART Must be greater than Two hundred and thirty Omega

One enter Two A model of output Two nothing HART function

Conversion accuracy: + 0.1%F.S

Temperature drift:. 0.01% F.S/ C

Dielectric strength: input / The output is more than 2000VAC ( 1min )

input / The power is greater than or equal to 2000VAC ( 1min )

output / The power is greater than or equal to 1000VAC ( 1min )

Insulation resistance: input / output / The power is greater than or equal to 100M (omega 500VDC )

Remarks: One enter One A model, One , Three , Eleven , Twelve Don't pick feet up; One enter Two A model, One , Three Don't pick feet up.

      The toggle switch is arranged near one side of the base, the input signal is Four Wire (isolation mode); on the contrary, forTwo Wire (distribution mode).

 

For details please download:MDSC322E series distribution isolator (HART)