Hello!Welcome to Madshen.
hotsearch
MDSB343E series thermocouple thermal isolation type safety g

 

undefined

function
MDSB343E series of thermocouple temperature isolation type Safety gate The power supply circuit. The scene K , S , E , B , R , T ,, N Thermocouple etc. sensor The output signal, After isolating the linear processing, and converted into a linear relationship with the temperature. Two Wire current signal output. The output circuit of power supply, power does not need to work independently. Online index number and temperature range. Optional One enter One A. Isolated gate From the terminal energy into the limit of intrinsically safe dangerous places, so as to ensure the safety and explosion-proof system.

 

Type specification

Product model

1 input code

2 input code

The output of the 1 code

The output of the 2 code

MDSB343E-

1:K type thermocouple

0: input 2

C:4~20mADC

0: output 2

2:S type thermocouple




3:E type thermocouple




4:B type thermocouple




5:R type thermocouple




6:T type thermocouple




7:J type thermocouple




8:N type thermocouple




G: other thermocouple




 

 

  Undefined

Explosion-proof technology index

Explosion proof mark: [Exia Ga] II C

Authentication parameters: (terminal 4/6 Between)

Um=250V Uo=6.6V Io=68mA

Po=113mW Co=5 Mu F Lo=5mH

 

 

Product features:

The input and output power, the three party is completely isolated, strong anti-interference ability

High precision, high linearity, high stability

Modular design, small volume, low power consumption, suitable for intensive installation

Reasonable structure, easy plugging, installation, disassembly and maintenance is more convenient and simple

 

 

Technical indicators

Input signal: K , S , E , B , R , T , J And the danger zone

Cold end compensation: 0~50 Degree of error One C

Output signal: Two Wire 4~20mA The safety zone,

Output voltage: 16~30V That is, the operating power supply voltage

Conversion accuracy: + (0.2%F.S Delta V>10mV)

          . 0.4%F.S (10mV More than Delta V More than 5mV)

Temperature drift:. 100ppm/ C

Dielectric strength: input / The output is more than 2000VAC ( 1min )

          Intrinsically safe / Non intrinsically safe, more than 2000VAC ( 1min )

Insulation resistance: input / The output is more than 100M (omega 500VDC )

 

Remarks: Safety gate The connection between the thermocouple compensation wire to must use the same type, otherwise it will increase the measurement error.

CJC For the cold end compensation of thermocouple, has been fixed on the special terminal.

DCS The Board shall be provided for Two Wire input mode (distribution mode).

 

Please download the data selection: MDSB343E series of thermocouple temperature isolation gate circuit power supply


 

 

 

Browse:
Return To The Top

分享到: