Hello!Welcome to Madshen.
hotsearch
MDSB313E series DC millivolt signal safety barrier

 

undefined


function

MDSB313E series DC millivolt signal Isolated Safety gate DC millivolt signal receiving site, After isolated output, usually used to isolate the thermocouple signal. Optional One enter One A. Isolated gate From the terminal energy into the limit of intrinsically safe dangerous places, so as to ensure the safety and explosion-proof system.


Type specification

Product model

1 input signal

2 input signal

The 1 output signal

The 2 output signal

MDSB313E-V0V0

-5~60mV

No input 2

-5~60mV

Output 2

 

 

  Undefined

 

Explosion-proof technology index

Explosion proof mark: [Exia Ga] II C

Authentication parameters: (terminal 4/6 Between)

Um=250V Uo=6.6V Io=68mA

Po=113mW Co=5 Mu F Lo=5mH

 

 

Product features:

The input and output power, the three party is completely isolated, strong anti-interference ability

High precision, high linearity, high stability

Modular design, small volume, low power consumption, suitable for intensive installation

Reasonable structure, easy plugging, installation, disassembly and maintenance is more convenient and simple

 

 

Technical indicators

The working power supply: 24VDC . 10%

Work    Consumption: less than or equal to 0.6W

Input signal: -5~60mV And the danger zone

Input impedance: More than 10M Omega

Output signal: -5~60mV The safety zone,

Output impedance: Less than or equal to Ten Omega (internal impedance)

Conversion accuracy: + Four 0uV

Temperature drift:. Four UV / C

Dielectric strength: input / output / The power is greater than or equal to 1500VAC ( 1min )

          Intrinsically safe / Non intrinsically safe, more than 1500VAC ( 1min )

Insulation resistance: input / output / The power is greater than or equal to 100M (omega 500VDC )

Remarks: Safety gate The connection between the thermocouple compensation wire to must use the same type, otherwise it will increase the measurement error.

 

Please download the data selection: MDSB313E series DC millivolt signal Isolated gate


 

Tags: MDSB313E   dc millivolt signal   isolated safety grid  