Author:
madshen Add Time:2014-03-30 15:16:26

function
MDSB306E series Detection of isolated converter Safety gate yes Linear voltage or current signal, receiving a dangerous place after isolation, transformed into linear signal output to the user specified, safe area. Optional One enter One A, One enter TwoA, Two enter Two A. Isolated gate From the terminal energy into the limit of intrinsically safe dangerous places, so as to ensure the safety and explosion-proof system.
Type specification
Product model | 1 input code | 2 input code | The output of the 1 code | The output of the 2 code |
MDSB306E- | 1:0~1VDC | 1:0~1VDC | 1:0~1VDC | 1:0~1VDC |
2:0~5VDC | 2:0~5VDC | 2:0~5VDC | 2:0~5VDC |
3:1~5VDC | 3:1~5VDC | 3:1~5VDC | 3:1~5VDC |
4:0~10VDC | 4:0~10VDC | 4:0~10VDC | 4:0~10VDC |
A:0~10mADC | A:0~10mADC | A:0~10mADC | A:0~10mADC |
B:0~20mADC | B:0~20mADC | B:0~20mADC | B:0~20mADC |
C:4~20mADC | C:4~20mADC | C:4~20mADC | C:4~20mADC |
G: other signals | G: other signals | G: other signals | G: other signals |
| 0: input 2 |
| 0: output 2 |

Explosion-proof technology index
Explosion proof mark: [Exia Ga] II C
Authentication parameters: (terminal 4/6 Between, 1/3 Between)
Um=250V Uo=28V Io=93mA
Po =655mW Co=50nF Lo=2.4mH
Technical indicators
The working power supply: 24VDC . 10%
Work Consumption: less than or equal to 1.2W ( One enter One A)
Less than or equal to 1.8W ( One enter Two A)
Less than or equal to 2.4W ( Two enter Two A)
Input signal: DC current or voltage signal, the danger zone
Input impedance: current input is less than or equal to Two hundred Omega;
The input voltage is greater than or equal. 500K Omega
Output signal: DC current or voltage signal, the safety zone
Output: output current, 0~350 Omega;
The output voltage is greater than or equal. 10K Omega
Conversion accuracy: + 0.2%F.S
Temperature drift:. 0.01% F.S/ C
Dielectric strength: input / The output is more than 2000VAC ( 1min )
input / The power is greater than or equal to 2000VAC ( 1min )
output / The power is greater than or equal to 1000VAC ( 1min )
Intrinsically safe / Non intrinsically safe, more than 2000VAC ( 1min )
Insulation resistance: input / output / The power is greater than or equal to 100M (omega 500VDC )
Product features:
The input and output power, the three party is completely isolated, strong anti-interference ability
High precision, high linearity, high stability
Modular design, small volume, low power consumption, suitable for intensive installation
Reasonable structure, easy plugging, installation, disassembly and maintenance is more convenient and simple
Remarks: One enter One A model, One , Three , Eleven , Twelve Don't pick feet up; One enter Two A model, One , Three Don't pick feet up.
Common specifications selection examples:
Model:MDSB306E-20C0
Input: 0-5VDC signal
Output1:4-20mADC signal
Aux.power:24VDC
Description: This product is a DC power supply type detection terminalThe conversion and isolationSafety gate, 0-5VDC signal Input, After isolating the output after treatment4-20mADCThe auxiliary power supply for 24VDC. signal;
For details please download: The conversion of MDSB306E detection terminal Isolated gate
Tags:
MDSB306E,检测端转换,隔离式安全栅
Browse: