Author:
madshen Add Time:2014-03-30 14:44:41

function
MDSB302E series The distribution of isolated end detection Safety gate (high power) To a dangerous place Two Wire TransmitterSupply, sampling Transmitter Output Two Wire current signal through the isolation after processing into Four Wire current signal output. Optional One enter One A, One enter Two A, Two enter Two A. Isolated gate From the terminal energy into the limit of intrinsically safe dangerous places, so as to ensure the safety and explosion-proof system.
Type specification
Product model | 1 input signal | 2 input signal | The 1 output signal | The 2 output signal |
MDSB302E-C0C0 (high power) | 4~20mADC | No input 2 | 4~20mADC | Output 2 |
MDSB302E-C0CC (high power) | 4~20mADC | No input 2 | 4~20mADC | 4~20mADC |
MDSB302E-CCCC (high power) | 4~20mADC | 4~20mADC | 4~20mADC | 4~20mADC |

Explosion-proof technology index
Explosion proof mark: [Exia Ga] II C
Authentication parameters: (terminal 4/6 Between, 1/3 Between)
Um=250V Uo=28V Io=119mA
Po =833mW Co=30nF Lo=1mH
Product features:
The input and output power, the three party is completely isolated, strong anti-interference ability
High precision, high linearity, high stability
Modular design, small volume, low power consumption, suitable for intensive installation
Reasonable structure, easy plugging, installation, disassembly and maintenance is more convenient and simple
Technical indicators
The working power supply: 24VDC . 10%
Work Consumption: less than or equal to 1.2W ( One enter One A)
Less than or equal to 1.8W ( One enter Two A)
Less than or equal to 2.4W ( Two enter Two A)
Input signal: danger zone, Two Wire 4~20mA
Distribution voltage: 19V@20mA
Distribution: the maximum short-circuit current protection, 40mA
The maximum open circuit voltage, 28V
Output signal: Four Wire 4~20mA The safety zone,
Output load: 0~350 Omega
Conversion accuracy: + 0.15%F.S
Temperature drift:. 0.01% F.S/ C
Dielectric strength: input / The output is more than 2000VAC ( 1min )
input / The power is greater than or equal to 2000VAC ( 1min )
output / The power is greater than or equal to 1000VAC ( 1min )
Intrinsically safe / Non intrinsically safe, more than 2000VAC ( 1min )
Insulation resistance: input / output / The power is greater than or equal to 100M (omega 500VDC )
Remarks: One enter One A model, One , Three , Eleven , Twelve Don't pick feet up; One enter Two A model, One , Three Don't pick feet up.
Common specifications selection examples:
Model:MDSB302E (high power -C0C0-1212)
Input: 4-20mADC signal
Output1:4-20mADC signal
Aux.power:24VDC
Description: This product is a high end distribution isolation into a detectionSafety gate, input :A road safety zone, 4-20mADC, output: danger zone, road 4-20mADC, power: DC24V
For details please download: MDSB302E series of testing terminal distribution Isolated gate (high power)
Tags:
MDSB302E detection end distribution isolation type safety grid (high distribution)
Browse: