Author:
madshen Add Time:2014-04-01 16:34:54

function
MDSB345E series potentiometer transmission Isolated Safety gate The power supply circuit. The receiving of dangerous places (slide wire potentiometer) signal, after the isolation process, transform into linear resistance Two Wire current signal output. The output circuit of power supply, power does not need to work independently. Optional One enter One A. Isolated gateFrom the terminal energy into the limit of intrinsically safe dangerous places, so as to ensure the safety and explosion-proof system.
Type specification
Product model | 1 input code | 2 input code | The output of the 1 code | The output of the 2 code |
MDSB345E- | 1:0~100 potentiometer | 0: input 2 | C:4~20mADC | 0: output 2 |
2:0~1k potentiometer |
|
|
|
3:0~5k potentiometer |
|
|
|
4:0~10k potentiometer |
|
|
|
5:0~20k potentiometer |
|
|
|
G: other resistance |
|
|
|

Explosion-proof technology index
Explosion proof mark: [Exia Ga] II C
Authentication parameters: (terminal 1/4 , 1/6 , 4/6 Between)
Um=250V Uo=6.6V Io=68mA
Po=113mW Co=5 Mu F Lo=5mH
Product features:
The input and output power, the three party is completely isolated, strong anti-interference ability
High precision, high linearity, high stability
Modular design, small volume, low power consumption, suitable for intensive installation
Reasonable structure, easy plugging, installation, disassembly and maintenance is more convenient and simple
Technical indicators
Input signal: the maximum range 0~20 K Omega, danger zone
The excitation current is less than or equal to: 2mA
Output signal: Two Wire 4~20mA The safety zone,
Output voltage: 16~30V That is, the operating power supply voltage
Conversion accuracy: + 0.2%F.S
Temperature drift:. 150ppm/ C
Dielectric strength: input / The output is more than 2000VAC ( 1min )
Intrinsically safe / Non intrinsically safe, more than 2000VAC ( 1min )
Insulation resistance: input / The output is more than 100M (omega 500VDC )
S>)
Temperature drift:. 100ppm/ C
Dielectric strength: input / The output is more than 2000VAC ( 1min )
Intrinsically safe / Non intrinsically safe, more than 2000VAC ( 1min )
Insulation resistance: input / The output is more than 100M (omega 500VDC )
Remarks: DCS The Board shall be provided for Two Wire input mode (distribution mode).
Please download the data selection: MDSB345E series variable potentiometer isolating gate circuit power supply
Browse: